Variant in Current Transformer: Core Balance Current Transformer (CB CT)
The CBCT, also known as a zero sequence CT, is used for earth leakage and earth fault protection. The concept is similar to the RVT. In the CBCT, the three core cable or three single cores of a three phase system pass through the inner diameter of the CT.
When the system is fault free, no current flowns in secondary of the CBCT. When there is an earth fault, the residual current (zero phase sequence current) of the system flows through the secondary of the CBCT and this operates the relay. In order to design the CBCT, the inner diameter of the CT, the relay type, the relay setting and the primary operating current need to be furnished.
Feature | Value |
---|---|
Input Specifications | |
Current Transformer Type | Core Balance Current Transformer |
Operating Current Range | 10mA - 30A |
Environmental Specifications | |
Operating Temperature | 0⁰ to 55⁰ C |
Torage Temperature | -20⁰ to 75⁰ C |
Humidity (non - condensing) | Upto 95% RH |
Mechanical Specifications | |
Mounting | Panel |
Wire Size (max) | 0.2 - 1.5mm (AWG : 24 - 14) |
Screw Tightening Torque | 0.5 N.M |
Inner Diameter | 30 MM | 80 MM | 115 MM | 210 MM |