Core Balance Current Transformer (CB CT)

Core Balance Current Transformer (CB CT)

Variant in Current Transformer: Core Balance Current Transformer (CB CT)

The CBCT, also known as a zero sequence CT, is used for earth leakage and earth fault protection. The concept is similar to the RVT. In the CBCT, the three core cable or three single cores of a three phase system pass through the inner diameter of the CT.

When the system is fault free, no current flowns in secondary of the CBCT. When there is an earth fault, the residual current (zero phase sequence current) of the system flows through the secondary of the CBCT and this operates the relay. In order to design the CBCT, the inner diameter of the CT, the relay type, the relay setting and the primary operating current need to be furnished.

Standard Features:
  • Zero Phase Sequence CT.
  • Used for earth leakage and earth fault protection.
  • Concept is similar to the RVT.
  • Inner Diameter: 30 MM | 80 MM | 115 MM | 210 MM.
Feature Value
Input Specifications
Current Transformer Type Core Balance Current Transformer
Operating Current Range 10mA - 30A
Environmental Specifications
Operating Temperature 0⁰ to 55⁰ C
Torage Temperature -20⁰ to 75⁰ C
Humidity (non - condensing) Upto 95% RH
Mechanical Specifications
Mounting Panel
Wire Size (max) 0.2 - 1.5mm (AWG : 24 - 14)
Screw Tightening Torque 0.5 N.M
Inner Diameter 30 MM | 80 MM | 115 MM | 210 MM

Note: Technical Specifications and illustrations are subject to change arising out of continuous Product Development.

Related Products for Digital Meter

Copyright © 2023 Powertrac Meters Pvt Ltd | All Rights Reserved | Designed By :   Aunicode International

// disable viewing page source